Moving Violations Video No. 198: Yet Another Dedicated Space Violation

2019-09-11 18:12:00| Electrical Construction & Maintenance

Section 110.26(E)(1)(a) of the 2017 NEC outlines the dedicated electrical space requirements around electrical equipment. As Russ shows us in this video, the drain pipe for a large drip pan runs directly above a panelboard. Its definitely not locate

Tags: video space moving dedicated

 

Moving Violations Video No. 197: Undedicated

2019-08-22 15:59:00| Electrical Construction & Maintenance

Section 110.26(E)(1) of the 2017 NEC outlines the dedicated space requirements around electrical equipment. As Russ shows us in this video, an electrician or an HVAC technician violated this rule. The A/C duct and grille is sitting about 4 ft above t

Tags: video moving violations moving video

 
 

Moving Violations Video No. 196: Sloppy Support and Missing Seal

2019-08-07 16:35:00| Electrical Construction & Maintenance

In this video, Russ finds a metal box thats improperly supported by MC cables. The installation violates the requirements of Sec. 314.23 of the 2017 NEC. The box is also missing a knockout seal, which is a violation of Sec. 110.12.

Tags: video support moving missing

 

Moving Violations Video No. 195: Yet Another Support Failure

2019-07-24 17:03:00| Electrical Construction & Maintenance

In this video, Russ shows us a violation of NEC Sec. 350.30(A). These -in. and 1-in. liquidtight flexible metal conduits (LFMCs) should be supported within 12 in. of the cabinet or box and at intervals of no more than 4 ft (an Exception allows 3 ft

Tags: video support moving failure

 

Moving Violations Video No. 194: Can't Hang with This

2019-07-11 17:04:00| Electrical Construction & Maintenance

Russ finds a dangling receptacle outlet box hanging off the end of a run of electrical metallic tubing.

Tags: this video moving hang

 